Alarm signalling with lights

Alarm signalling with lights

An ongoing alarm is signalled by the outdoor siren, both acoustically and by flashing. This signalling is limited in time, though, and many owners look for a way to alert the neighbourhood to the attacked building for longer. One option is to make the building's lights flash like warning lights. This works especially well where the building has large glazed areas and the flashing light is clearly visible.

The JABLOTRON 100+ security system can switch lighting through the AC-160-C, AC-160-DIN, JA-110N or JA-150N output modules. If these modules are already installed in the building to switch lights, you can use them. If not, you can add them to switch selected lights in parallel.

Required equipment

Control panel

Radio module

Power module

Other

  • F-Link 2.7.0 and higher

Wiring

  • This procedure assumes that you are familiar with the manuals of the products used.

  • Use the AC-160-C, AC-160-DIN, JA-110N or JA-150N output modules already installed, or install them, see the example for the JA-150N below.

    • Connect the L and N wires to the mains supply terminal
    • Connect the 230V and COM terminals
    • The NO terminal will switch the phase when the PG is activated
    • Connect output L and N to the lighting terminal block, see Figure 1. WARNING! The maximum switching load of the relay is 16A !

Wiring

Only qualified personnel may connect mains devices.
The product is used for functional single-pole switching and does not provide safe disconnection.

Wiring

Figure 1 – Wiring diagram for the JA-150N power relay

Setting up and programming the system

The example uses eight PG outputs in total. Outputs PG1 and PG2 are two connected lighting circuits; PG3 to PG8 make the lights flash and then stop the flashing after unsetting, or once a defined time after the alarm has passed. WARNING: logging to memory must be enabled for PG3 to PG8. You make all the settings in F-Link on the Settings/PG outputs tab.

Setting up and programming the system

  1. If PG1 and PG2 already switch two lighting circuits, start by setting PG3 with the "On/Off" function, switched in reaction to "Any alarm". If the building has more sections, it is best to enable all of them.

Setting up and programming the system

  1. Next, set PG4, which makes the lights flash. Set the "Impulse" function to 3 seconds, switch it in reaction to "Other PG" and select PG3 and PG6.

Setting up and programming the system

  1. PG5 provides the pause between flashes. Set it to the "Impulse" function for 3 seconds as well, switch it in reaction to "Event in system" and select "PG output 4 off".

Setting up and programming the system

  1. Close the loop by setting PG6. Again set the "Impulse" function to 3 seconds, switch it in reaction to "Event in system" and select "PG output 5 off".

Setting up and programming the system

  1. PG7 stops the warning flashing when the alarm is switched off. Set it to "Impulse" for 10 seconds, switch it in reaction to "Unset" and select the sections.

Setting up and programming the system

Then link this PG to PG4: in PG4, set "PG blocking" by "Other PG" and select PG7. When the selected sections are unset, the flashing loop is blocked.

Setting up and programming the system

  1. PG8 stops the warning flashing after a set time. You can set the total time of the warning flashing to, for example, 30 minutes. Always agree this time with the building owner and take the type of lighting into account so that it is not damaged. Set PG8 to the "Impulse" function for 30 minutes, switch it in reaction to "Any alarm" and set the same sections as for PG3.

Setting up and programming the system

Then link this PG to PG5: in PG5, set "PG blocking" by "Other PG", select PG8 and "by deactivation". When the set time from the start of the alarm has passed, PG8 deactivates, which blocks the flashing loop.

Setting up and programming the system

  1. The last step is to tie the PG outputs that switch the lights directly to this loop. If, as at the start, the lights are switched by PG1 and PG2, set their reaction to "Other PG" and select PG4.

Setting up and programming the system