JA-150EM-DIN
Wireless module for the impulse output of an electric meter
A wireless module that reads the pulse output of an electricity meter and sends it to the control unit. It does not switch anything and does not measure consumption itself; it only passes on the reading from the electricity meter already installed in the building. The reading is for information only and is not intended for billing.
Product line
- JABLOTRON 100+
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Power
- 230V/50 Hz, protection class II.
- Power consumption typical/maximum
- approx. 0.5 W /1.2 W (230 V AC)
- Maximum current consumption
- 10 mA
- Communication band
- 868.1 MHz, Jablotron protocol
- Radio communication module
- TRX-30
- Antenna
- Internal with a possibility to connect external antenna type AN-868
- IN input
- low voltage, galvanically separated from mains, operating voltage 5 V, maximum external overvoltage 30 V DC, maximum connection cable length 3 m.
Basic description
Compared with the JB-164N-PLUG smart plug with consumption monitoring, the difference is fundamental: the plug measures the consumption of whatever is plugged into it, whereas the JA-150EM-DIN does not measure any consumption itself, it only reads the pulse output of the electricity meter the customer already has installed, and it does not switch anything at all.
- Turns the pulse output of a standard electricity meter into a value visible in the system. The electricity meter is not rewired and no cable is run to the control unit.
- It transmits using the JABLOTRON wireless protocol and is powered directly from the mains; no cable runs to the control unit.
- It has three input terminals with different roles: PU for the pulse output of the electricity meter, IN for general use and TA for the tariff switching signal from the ripple control (HDO) receiver.
Why choose this product
What the module reads and sends
The module counts the pulses from the connected electricity meter and forwards them to the control unit together with the tariff status.
- The PU input is galvanically isolated from the mains and is intended for the S0 pulse outputs of class B electricity meters according to EN 62053-31.
- The TA input distinguishes the low and high tariff according to the ripple control (HDO) signal; the module can be operated in factory mode A, or in mode B with inverted logic of the TA input via the IN input.
- With power supply surveillance enabled, the module reports a fault if the power supply is missing for longer than 1 hour.
What the system needs for it
The module is a peripheral of the control unit; you enrol it to the selected position in the F-Link program on the Devices tab.
- The control unit must be fitted with a JA-11xR radio module. The F-Link program must be version 1.2.0 or higher.
- The PU and IN inputs work at 5 V and withstand an external overvoltage of up to 30 V DC; the wire to them must be no longer than 3 metres.
- The PU input has a 10 ms time filter, the IN input 400 ms.
Where it is installed and what it can withstand
It is mounted on a DIN rail and connected directly to the mains; the pulse output of the electricity meter and, optionally, the tariff switching signal from the ripple control (HDO) receiver are then connected to its terminals.
- Own consumption typically 0.5 W, no more than 1.2 W at 230 V AC; current draw up to 10 mA.
- Outdoor protected environment, operating temperature −20 °C to +60 °C, IP40 ingress protection on the front panel.
- The antenna is internal, with the option of connecting an external AN-868 antenna if the location of the distribution board requires it.
Frequently asked questions
No. The module only serves to display the electricity meter reading in the system for information; it is not intended for billing.
Not with every one. It works with electricity meters that have a class B S0 pulse output according to EN 62053-31. The PU input also accepts a volt-free pulse output or an open-collector output switching to GND.
Technical specifications
- Power
- 230V/50 Hz, protection class II.
- Power consumption typical/maximum
- approx. 0.5 W /1.2 W (230 V AC)
- Maximum current consumption
- 10 mA
- Communication band
- 868.1 MHz, Jablotron protocol
- Radio communication module
- TRX-30
- Antenna
- Internal with a possibility to connect external antenna type AN-868
- IN input
- low voltage, galvanically separated from mains, operating voltage 5 V, maximum external overvoltage 30 V DC, maximum connection cable length 3 m.
- PU input
- low voltage, galvanically separated from mains, operating voltage 5 V, maximum external overvoltage 30 V DC, maximum connection length 3 m, compatible with an impulse SO output of class B electricity meters according to EN 62053-31
- TA input
- remote tariffing input maximum 230 V AC
- Dimensions
- 68 x 96 x 18 mm, 1 DIN module
- Operational environment
- general outdoor -20 to +60 °C
- IP covering
- front panel IP40 according to EN 60529
- Can be operated to
- ERC REC 70-03
- Complies with
- ETSI EN 300 220-1, EN 50130-4, EN 55022, EN 60950-1
Warning
- The reading from the module is for information only and cannot be used for billing consumption or for resolving a dispute with the energy supplier. Connection to the mains may only be carried out by a person with the appropriate electrical qualifications. When connecting to the electricity meter, no sealed part of the distribution board may be damaged; where the distribution network operator does not allow access, use an additional electricity meter located outside that distribution board. The polarity on the PU input must be observed according to the type of meter output, otherwise the module will not register the pulses correctly.
Installation example
Connection to the mains may only be carried out by a person with the appropriate electrical qualifications.
Fix the module to a DIN rail and connect it to the mains at the L and N terminals.
Connect the pulse output of the electricity meter to the PU and COM terminals, observing the polarity: PU to S0+, COM to S0-.
Optionally, connect the tariff switching signal from the ripple control (HDO) receiver to the TA terminal; the wire on the TA terminal must be on the same phase as the supply wire on the L terminal.
Select mode A or mode B according to how the TA input is connected.
In the F-Link program version 1.2.0 or higher, select the required position on the Devices tab and switch on enrolment with the Enrol button.
Pressing the LEARN / Set button for 1 s makes the module send the enrolment signal and enrol to the selected position.