JA-150ST
Wireless fire and temperature detector
When it detects smoke or a high temperature, it starts flashing and transmits the alarm to the system at the same time.
Product line
- JABLOTRON 100+
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Power
- 3x LR6 (AA) type alkaline batteries, 1.5 V Warning: batteries are not included
- Typical battery lifetime
- approx. 3 years
- Communication band
- 868.1 MHz, Jablotron protocol
- Effective Radiated Power (ERP)
- 10 mW
- Communication range
- approx. 300 m (unrestricted area)
- Dimensions
- diameter 126 mm, height 50 mm
- Weight
- 150 g
Basic description
The detector picks up a fire as it starts and gives you time to respond or to evacuate in good time. Besides transmitting the alarm to the system, it also signals the fire by flashing the LED on the detector itself.
- Fire signalled by the LED flashing on the detector and also by the system keypads and sirens
- Remote alerting in MyJABLOTRON and to the Alarm Receiving Centre
- Thanks to the heat sensor, it also reacts to a fire without dense smoke (flammable liquids and the like)
Why choose this product
Where the detector can be used
Smoke detection is intended for interiors without increased dust levels, which can cause false alarms. If necessary, the reaction to smoke can be disabled.
- Detection of smoke and of high temperature in flats and houses
- Optionally a slower reaction to heat only, or both conditions required at the same time
- In enclosed interiors where smoke rises all the way to the ceiling
Placement
The number of detectors depends on the size and layout of the flat or house. The minimum is one detector on the escape route from the flat, plus one more in another part in a flat over 150 m². In a multi-storey flat or family house, a detector belongs above the stairwell as well. Ideally, cover all the rooms where people sleep too.
- If possible the centre of the ceiling, where air circulation carries the smoke
- Parts of a room divided by shelving or partitions reaching almost to the ceiling, each as a separate room
- A narrow space, where the detector belongs in the middle third of its width
Where not to put the detector
Do not place the detector where poor air circulation could prevent smoke from reaching it. At the same time, avoid places with dust, cigarette smoke or steam, where false alarms are a risk.
- In kitchens, bathrooms, laundry rooms or other damp areas
- Directly at air-handling or air conditioning outlets, where the air flow is strong
- In niches, corners and apexes of sloping ceilings, where the air circulates poorly
Frequently asked questions
It is a system fire detector according to EN 54: it reports the alarm to the control unit. Where the control unit forwards it depends on the system configuration and on the services agreed. The JA-151ST version has its own siren for an immediate warning in the room.
The optical smoke sensor is sensitive, and cigarette smoke in larger quantities can activate it. Do not install it in smoking rooms or in kitchens directly above the cooker.
Once every 30 days: the optical part with a test spray, the heat part with a stream of hot air. Never test the detector with a naked flame.
Technical specifications
- Power
- 3x LR6 (AA) type alkaline batteries, 1.5 V Warning: batteries are not included
- Typical battery lifetime
- approx. 3 years
- Communication band
- 868.1 MHz, Jablotron protocol
- Effective Radiated Power (ERP)
- 10 mW
- Communication range
- approx. 300 m (unrestricted area)
- Dimensions
- diameter 126 mm, height 50 mm
- Weight
- 150 g
- Smoke detection
- optical light scattering
- Smoke detector sensitivity
- m = 0.11 - 0.13 dB/m pursuant to EN 54-7
- Heat detection
- class A2 according to EN 54-5
- Alarm temperature
- +60 °C to +70 °C
- Operating temperature range
- -10 °C to +80 °C
- Complies with
- EN 54-5, EN 54-7, EN 54-25
- Also complies with
- ETSI EN 300220, EN 50130-4, EN 55022, EN 60950-1
- Can be operated according to
- ERC REC 70-03
- Recommended screw
- 2x o 3.5 x 40 mm (countersunk head)
Warning
- The control unit must contain a radio module. Install it on the ceiling, not on a wall, at least 0.5 m away from walls. Do not install it in kitchens, bathrooms or dusty areas. Above a floor area of 150 m², add another detector. After the detector is closed, an automatic test runs for about a minute, during which the detector does not detect. Fit it in one position only, following the arrows. Carry out a test once every 30 days, check the signal strength and clean the dust off regularly.
Installation example
Fix the detector to the ceiling so that smoke can reach it through natural thermal circulation; keep at least 0.5 m away from walls, partitions and corners.
Insert three AA (LR6) alkaline batteries.
The control unit must have a JA-11xR radio module. Enrol the detector according to the control unit manual.
Accessories
Related products

JA-152P
Wireless PIR motion detector

JA-159P
Wireless outdoor PIR detector

JA-161PW
Wireless PIR and MW combined detector

JA-162PW
Wireless dual PIR and MW motion detector

JA-162PC
Wireless PIR motion detector with a 90° verification camera

JA-153M
Wireless magnetic detector with recognition of external magnetic fields

JA-150M
Wireless magnetic detector with 2 universal inputs

JA-155M
Wireless mini magnetic detector

JA-180PB
Wireless PIR and glass-break combined detector

JA-151ST
Wireless combined smoke and heat detector with built-in siren

JB-EXT-TH-R
Wireless outdoor thermometer

JA-151TH
Wireless temperature detector
Help us improve the catalog
Missing something, or found a mistake? Let us know.