EI208DW

Stand-alone carbon monoxide detector with display

Discontinued

A stand-alone carbon monoxide detector with an information display. In addition to the LED and the built-in siren, it also shows the measured concentration in ppm. Connection to the system is provided by the JA-110G-CO or JA-150G-CO plug-in module.

Compatibility

JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K

Check compatibility

Key specifications

Usable life
the end of life date is stated on the label
Power
Integrated non-replaceable lithium battery
Typical battery lifetime
for the whole usable life of the detector
Operating temperature range
0 °C to +40 oC
Humidity range
15% to 95% (non-condensing)
Dimensions, weight
120 x 105 x 40 mm, 170 g
Conformity
EN 50291-1; EN 50291-2, EN 50270

Basic description

The display is the only difference from the EI208W; both models share all other technical values. Where the customer does not need a display and visual and audible signalling are enough, choose the EI208W.

  • Information display. Shows the measured CO concentration in ppm from 20 ppm upwards.
  • Stand-alone operation. Warns with an LED, the display and a built-in siren even without a control unit.
  • Integration via the JA-110G-CO or JA-150G-CO plug-in module. Both the start and the end of an alarm are reported to the control unit.
  • Service life of 10 years. With the JA-150G-CO module, 8 years; the date on the label is decisive.

Why choose this product

A specific value on the display

The information display adds the specific measured carbon monoxide value to the visual and audible signalling, so the user sees not only that something is happening but also how much. Below the threshold from which the value is displayed, the numeric field stays blank; the reading on the display therefore does not replace the prescribed function test. Once fitted onto the base, the detector starts up by itself, and all the display symbols light up when it has started successfully.

  • CO concentration in ppm from 20 ppm upwards
  • Icons for low battery, sensor fault and end of service life
  • Built-in siren and LED during an alarm

Where a display pays off

A display pays off where the customer or facility manager wants to see the measured concentration rather than just wait for an alarm. Otherwise the same rule applies as for the version without a display: a separate detector belongs in every room with a source of carbon monoxide and wherever people sleep. Caravans and boats are also an intended environment.

  • Boiler rooms and plant rooms under permanent surveillance
  • Bedrooms and rooms where people stay for long periods
  • Buildings with regular technical inspections

Testing and service life

Check the function immediately after installation and then once a week by pressing the button, as well as after a longer absence and after every service of the fuel-burning appliance. In addition, test the detector with CO test gas once a year. The detector reports a low battery, a sensor fault and the end of its service life by itself, with a distinct icon, flashing and beeping.

  • Have the installation carried out by a trained technician
  • On a wall 15 cm below the ceiling, on the ceiling 30 cm from walls, with no CO source 1 to 2 m high
  • The sensor cannot be calibrated; the whole detector is replaced

Frequently asked questions

Help us improve the catalog. Missing something, or found a mistake? Let us know.