JA-150G-CO
Wireless module for connection of an Ei208W(D) CO detector
A wireless plug-in module that you insert directly into the Ei208W or Ei208DW stand-alone CO detector. It then reports the start and end of an alarm, detector switch-off and battery status to the JABLOTRON 100+ system by radio. It is powered from the detector's battery and has no power source of its own.
Product line
- JABLOTRON 100+
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Power
- from Ei208(D)W battery
- Communication frequency
- 868.1 MHz, Jablotron protocol
- Maximum radio-frequency power (ERP)
- 6 mW
- RF range
- approx. 300 m (open area)
- Dimensions
- 109 x 24 x 22 mm
- Environmental class
- II. Indoor general (acc. EN 50131-1)
- Operational temperature range
- -10 °C to +40 °C
Basic description
The JA-150G-CO provides the same system connection as the bus JA-110G-CO; they differ in power supply, dimensions and installation procedure. With this module, the usable life of the detector is shortened from 10 to 8 years.
- Wireless connection of the CO detector. Alarm to the control unit without running a cable.
- Powered from the detector's battery. The module has neither its own power source nor its own battery.
- 868.1 MHz band, JABLOTRON protocol. Range approximately 300 m in direct line of sight.
- Plug-in mounting. Inserted directly into the detector's system connector.
Why choose this product
What the module reports by radio
The module sits directly in the detector and passes the start and end of an alarm, detector switch-off and battery status from it to the control unit by radio. It has no power source of its own and takes its energy from the battery of the detector itself. The detector continues to warn with its siren on its own; the system merely adds remote information.
- Intended exclusively for Ei208W and Ei208DW detectors
- 868.1 MHz band, range approximately 300 m in direct line of sight
- Occupies one position in the system
Where there is no bus
The wireless version is suitable wherever a cable to the detector would mean interfering with finished surfaces. The CO leak alarm reaches the control unit; whether the user receives a message about it in the app or it is transmitted to an Alarm Receiving Centre (ARC) depends on the system configuration and the services agreed.
- Renovations without chasing into walls
- Boiler rooms and garages out of reach of the cabling
- Finished interiors where you do not want to interfere with surfaces
Installation and binding
The module can be enrolled in two ways: after switching on enrolment in F-Link, by closing the detector with the module inserted, or by entering the serial number in F-Link. Installation may only be carried out by a trained technician. The instructions of the CO detector itself then apply to placement, testing and normal operation.
- The module's antenna must sit in the space reserved for it
- Requires a JA-11xR radio module in the control unit
- With the module, the detector's service life is shortened to 8 years
Frequently asked questions
It connects the Ei208W or Ei208DW stand-alone CO detector to the JABLOTRON 100+ system wirelessly. It transmits the start and end of an alarm, detector switch-off and battery status.
Yes. Without the module, the usable life of the detector is 10 years; with the JA-150G-CO fitted, it is 8 years. The date on the detector's label is decisive.
A JA-11xR radio module. The module is not tied to a specific control unit model.
Technical specifications
- Power
- from Ei208(D)W battery
- Communication frequency
- 868.1 MHz, Jablotron protocol
- Maximum radio-frequency power (ERP)
- 6 mW
- RF range
- approx. 300 m (open area)
- Dimensions
- 109 x 24 x 22 mm
- Environmental class
- II. Indoor general (acc. EN 50131-1)
- Operational temperature range
- -10 °C to +40 °C
- Comply with
- ETSI EN 300 220-1, EN 50130-4, EN 55022, EN 60950-1, EN 50581
- Operational conditions
- ERC REC 70-3
Warning
- Installation may only be carried out by a trained technician. The module is plugged directly into the detector's system connector, not connected to it with a cable, and its antenna must sit in the space reserved for it. The control unit must have a JA-11xR radio module. The module is not a CO detector in its own right and detects nothing without an Ei208W or Ei208DW; the detector manual applies to placement and operation. The module occupies one position in the system. With the module fitted, the usable life of the detector is 8 years instead of 10 years.
Installation example
Check that the control unit has a JA-11xR radio module.
Insert the JA-150G-CO module into the system connector of the Ei208W or Ei208DW stand-alone detector; the antenna must sit in the space reserved for it.
In F-Link, select a position on the Devices tab and switch on enrolment, then enrol the module by closing the detector; alternatively, enter its serial number in F-Link.
Test the detector according to its own manual.
Related products

JA-152P
Wireless PIR motion detector

JA-159P
Wireless outdoor PIR detector

JA-161PW
Wireless PIR and MW combined detector

JA-162PW
Wireless dual PIR and MW motion detector

JA-162PC
Wireless PIR motion detector with a 90° verification camera

JA-153M
Wireless magnetic detector with recognition of external magnetic fields

JA-150M
Wireless magnetic detector with 2 universal inputs

JA-155M
Wireless mini magnetic detector

JA-180PB
Wireless PIR and glass-break combined detector

JA-150ST
Wireless fire and temperature detector

JA-151ST
Wireless combined smoke and heat detector with built-in siren

JB-EXT-TH-R
Wireless outdoor thermometer
Help us improve the catalog