GS-133
Gas Detector - 12 V DC
A separately powered detector of combustible gas leaks: natural gas, propane, butane and hydrogen. It distinguishes two concentration levels by LED and sound and offers a changeover relay output. It does not detect carbon monoxide; the EI208W is intended for that.
Product line
- JABLOTRON 100+
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Level 1
- 10± 3 % LEL (0.44 % vol. conc.), 18±3 % LEL (0.30% vol. conc.)
- Level 2
- 18±3 % LEL (0.80 % vol. conc.), 30±3 % LEL (0.50% vol. conc.)
- Level 1
- 23±3 % LEL (0.30 % vol. conc.), 9±3% LEL (0,36 % vol. conc.)
- Level 2
- 40±3 % LEL (0.50% vol. conc.), 16±3% LEL (0,66 % vol. conc.)
- Devices according to
- EN 50194-1, cl.1 type A
- Power supply
- 12 V DC ± 20 %
- Power consumption
- 100 mA (150 mA when relay is activated)
Basic description
The GS-133 is neither a bus nor a wireless peripheral and does not occupy a position in the system. It is connected to the security system via a relay output and powered separately from 12 V DC.
- Natural gas, propane, butane and hydrogen. Covers common gas appliances and pressurised cylinders.
- Two concentration levels. Distinct LED and acoustic signalling for each of them.
- Changeover relay C/NO/NC. Controls a gas shut-off valve, a security system or another warning.
- Own siren 94 dB / 0.3 m. Also warns locally; 12 V DC power supply.
Why choose this product
Two leak levels, not just an alarm
The detector monitors the concentration of combustible gas and distinguishes two levels, each with its own combination of visual and audible signalling. The operator can therefore tell on the spot which level the alarm concerns. An optional alarm memory also retains the information that a leak occurred, even if nobody was in the room.
- Natural gas, propane, butane and hydrogen
- Changeover relay C/NO/NC, switching at the 1st or 2nd level as selected
- Own siren 94 dB, 12 V DC power supply
Flats, boiler rooms and garages
The detector belongs wherever combustible gas is used and where a leak could go unnoticed for a long time. The relay output is connected to an input of the control unit or of an input module, so the alarm reaches the security system even when the building is empty. The environment must be free of any risk of explosion.
- Flats and residential buildings with gas appliances
- Boiler rooms and plant rooms
- Garages and spaces with propane or butane
Installation height according to the type of gas
The installation height decides whether the detector picks up a leak at all. Natural gas and methane are lighter than air and rise to the ceiling; propane and butane are heavier and stay close to the ground. Before installation, therefore, check which gas the customer uses, and do not install the detector where anything obstructs natural air circulation.
- Light gas: no more than 15 cm below the ceiling
- Propane and butane: near the floor, at the lowest point of the space
- Relay output to the security system
Frequently asked questions
Combustible gases: natural gas and methane, propane, butane and hydrogen. It does not detect carbon monoxide; the EI208W stand-alone detector is intended for that.
It depends on the type of gas. Natural gas and methane are lighter than air, so the detector is installed no more than 15 cm below the ceiling. Propane and butane are heavier, so the detector is installed near the floor, at the lowest point of the space.
Via the changeover relay output C/NO/NC to an input of the control unit or of an input module. On its own it is not an addressable peripheral and does not occupy a position in the system. It is powered with 12 V DC from an external source and is not battery-operated.
Technical specifications
- Level 1
- 10± 3 % LEL (0.44 % vol. conc.), 18±3 % LEL (0.30% vol. conc.)
- Level 2
- 18±3 % LEL (0.80 % vol. conc.), 30±3 % LEL (0.50% vol. conc.)
- Level 1
- 23±3 % LEL (0.30 % vol. conc.), 9±3% LEL (0,36 % vol. conc.)
- Level 2
- 40±3 % LEL (0.50% vol. conc.), 16±3% LEL (0,66 % vol. conc.)
- Devices according to
- EN 50194-1, cl.1 type A
- Power supply
- 12 V DC ± 20 %
- Power consumption
- 100 mA (150 mA when relay is activated)
- Detection method
- hot platinum filament
- Buzzer sound level
- 94 dB/0.3 m
- Relay output
- optional for 1st or 2nd level, max. 24 V AC / 2 A
- Alarm memory
- selectable
- Response time
- 20 s
- Warm up time
- approximately 90 s
- Working environment
- indoor use, -10 to +40°C, IP32D
- Working humidity
- max 80 %
- Designed to operate
- at normal atmospheric pressure 86 to 106 kPa
- Equipment according to
- EN 50194-1 type A
- Complies with
- EN 60079-29-1, EN 50130-4, EN, 50270, EN 55032, EN 62368-1. EN 50581
Warning
- Getting the installation height wrong means the detector will not pick up a leak in time; follow the type of gas the customer uses. The detector is intended only for spaces with no risk of explosion. Do not install it where natural air circulation is obstructed, where there is a lack of oxygen or where various odours could affect it (for example in a kitchen). Check the response using a gas lighter without a flame; the manufacturer recommends professional recalibration after one year of operation at the latest. The service life of the device is at least 5 years. In the event of an alarm, prevent the gas from igniting: do not touch electrical switches, ventilate thoroughly, prevent any further gas leakage and, if necessary, call the fire brigade or the gas supplier.
Installation example
Have the installation carried out by a person with the appropriate electrical qualifications.
Choose the height according to the type of gas: light natural gas and methane no more than 15 cm below the ceiling, heavier propane and butane near the floor at the lowest point of the space.
Do not install the detector near obstacles to natural air circulation, in places with a lack of oxygen, or where various odours could affect it (for example in a kitchen).
Connect the 12 V DC (±20 %) power supply.
Connect the changeover relay output C/NO/NC to an input of the control unit or of an input module; choose whether it should switch at the first or only at the second concentration level.
After switching on, wait for the sensor to stabilise (90 s) and check the response using a gas lighter without a flame.
Related products

JA-152P
Wireless PIR motion detector

JA-159P
Wireless outdoor PIR detector

JA-161PW
Wireless PIR and MW combined detector

JA-162PW
Wireless dual PIR and MW motion detector

JA-162PC
Wireless PIR motion detector with a 90° verification camera

JA-153M
Wireless magnetic detector with recognition of external magnetic fields

JA-150M
Wireless magnetic detector with 2 universal inputs

JA-155M
Wireless mini magnetic detector

JA-180PB
Wireless PIR and glass-break combined detector

JA-150ST
Wireless fire and temperature detector

JA-151ST
Wireless combined smoke and heat detector with built-in siren

JB-110N
Bus PG power output module
Help us improve the catalog
Missing something, or found a mistake? Let us know.