JA-110G-CO
Bus module for connection of an Ei208W(D) CO detector
A bus plug-in module that you insert directly into the Ei208W or Ei208DW stand-alone CO detector. It then reports the start and end of an alarm, detector switch-off and battery status to the JABLOTRON 100+ system via the bus. It detects nothing itself; the measuring is always done by the detector.
Product line
- JABLOTRON 100+
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Power
- from the control panel BUS 12 V (9 … 15 V)
- Current consumption in standby mode
- 5 mA
- Current consumption for cable choice
- 5 mA
- Dimensions
- 48 x 19 x 14 mm
- Environmental class
- II. indoor general (acc. EN 50131-1)
- Operational temperature range
- -10 °C to +40 °C
- Comply with
- EN 50130-4, EN 55022, EN 50581
Basic description
The JA-110G-CO provides the same system connection as the wireless JA-150G-CO; they differ in power supply, dimensions and installation procedure.
- Bus connection of the CO detector. The alarm travels to the control unit by cable.
- Powered from the 12 V bus. Standby consumption 5 mA, no battery of its own.
- Plug-in mounting. Inserted directly into the detector's system connector.
- Reports four events. The start and end of an alarm, detector switch-off and battery status.
Why choose this product
What the module reports to the system
The module plugs directly into the detector's system connector and passes the start and end of an alarm, detector switch-off and battery status from it to the control unit via the bus. It needs no power source of its own: the system cabling supplies it with both power and data. The detector remains stand-alone; the whole system simply knows about it now.
- Intended exclusively for Ei208W and Ei208DW detectors
- Powered from the 12 V bus, standby current 5 mA
- Occupies one position in the system
Where the bus is already run
A cable connection does not depend on the radio environment or on signal strength, so it is also suitable where there is a lot of interference nearby. The CO leak alarm reaches the control unit; whether the user receives a message about it in the app or it is transmitted to an Alarm Receiving Centre (ARC) depends on the system configuration and the services agreed.
- Boiler rooms with the bus run to them
- Plant rooms with cabling in place
- Premises with a high level of radio interference
Installation and operation
The progress of connection and enrolment is shown by the yellow LED directly on the module, so the technician can see the status even without a laptop. Do not forget the supplied silicone pad; otherwise a draught through the installation holes could affect the concentration measurement. The module is intended for an indoor – general environment, class II.
- Connect the bus with the power completely switched off
- Enrolment by closing the detector or by serial number in F-Link
- The CO detector instructions apply to operation and testing
Frequently asked questions
It connects the Ei208W or Ei208DW stand-alone CO detector to the JABLOTRON 100+ system via the bus. It transmits the start and end of an alarm, detector switch-off and battery status.
No, the module is intended exclusively for the Ei208W and Ei208DW.
Directly into the system connector inside the detector; it is not installed separately. Connect the bus to it with the system power completely switched off.
Technical specifications
- Power
- from the control panel BUS 12 V (9 … 15 V)
- Current consumption in standby mode
- 5 mA
- Current consumption for cable choice
- 5 mA
- Dimensions
- 48 x 19 x 14 mm
- Environmental class
- II. indoor general (acc. EN 50131-1)
- Operational temperature range
- -10 °C to +40 °C
- Comply with
- EN 50130-4, EN 55022, EN 50581
Warning
- Always connect the bus with the system power completely switched off. The module plugs directly into the detector's system connector; it is not connected to it with a short cable. Always use the supplied silicone pad, otherwise a draught through the installation holes will affect the CO measurement. The module is not a CO detector in its own right: the Ei208W(D) manual applies to placement, testing and operation. The module occupies one position in the system and requires one free position. The intended environment is II, indoor – general.
Installation example
Always connect the bus with the system power completely switched off.
Open the Ei208W or Ei208DW detector by turning it anticlockwise against the base.
Pass the cable through the supplied silicone pad and the detector base; the pad prevents air from flowing through the mounting holes, which would affect the CO measurement.
Fix the base to the wall so that the detector sits reliably against the silicone pad.
Connect the control unit bus to the module's terminal block.
Plug the module into the system connector in the detector; it is not connected by a cable. Make sure the cable does not push the module out of the detector.
After the system is switched on, the yellow LED flashes to show that the module is not enrolled. In F-Link, select the required position on the Devices tab and switch on enrolment mode with the Enrol option.
Fit the detector onto the base and secure it by turning it clockwise; the module is enrolled and the yellow LED goes off. The module can also be enrolled by entering its serial number in F-Link.
For operation and testing of the detector, follow the Ei208W(D) manual.
Related products

JB-110N
Bus PG power output module

JA-111TH
Bus temperature detector

JA-112P
Bus PIR motion detector

JA-110P
Bus PIR motion detector

JA-110P PET
Bus PIR motion detector with basic pet immunity

JA-115P
Bus ceiling PIR motion detector

JA-122PW
Bus dual PIR and MW motion detector

JA-122PB
Bus combined PIR motion and glass break detector

JA-122PC
Bus combined PIR motion detector with 90° photoverification camera

JA-120PC (90)
Bus PIR motion detector with 90° photo-verification camera

JA-120PC
Bus PIR Motion Detector with Camera

JA-111M
Mini bus magnetic detector
Help us improve the catalog
Missing something, or found a mistake? Let us know.