JA-111H-AD TRB

Bus module for system control

BUS module for connecting an external control device to the JABLOTRON 100+ system. It allows the system to be set and unset with that device and powers the device from the bus. Occupies one system position.

Compatibility

JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K

Check compatibility

Key specifications

Power
from control panel BUS 12 V DC (9 … 15 V)
Current consumption - Nominal consumption - to calculate backup
8 mA all inputs connected to GND (+ consumption of connected devices)
Current consumption - Maximal consumption - for cable selection
12 mA (+ consumption of connected devices)
Maximum allowed current of the connected detector
50 mA
Dimensions
16 x 30 x 12 mm
Weight
8 g
Classification
Security grade 2 / environmental class II

Basic description

The JA-111H-AD TRB connects an external control device, i.e. a device that controls the system by setting and unsetting it, to the JABLOTRON 100+ system. The AD suffix indicates precisely this use for system control, not for connecting a detector. A wired detector that reports its status is connected by the JA-111H TRB module; where several wired inputs are to be added at once, the JA-114HN or JA-116H is the right choice.

  • Connects an external control device. Use it to set and unset the system.
  • Control and power over one bus. The module also powers the connected control device.
  • Dimensions 16 × 30 × 12 mm, weight 8 g.
  • Fits into the system like any other peripheral. It occupies one position and reports to the control unit under its own address.

Why choose this product

System control by a third-party device

The module gives the system an interface through which even a device from another manufacturer can set and unset it. In the default setting, a single wire is enough and the system monitors its status; the second option works with two wires, one for setting and the other for unsetting. Polarity, reaction and delay are set in the configuration software, so the module adapts even to a device that was not originally designed for the system.

  • Single-wire status and pulse control
  • The INP input sets, the TRB input unsets
  • Controls programmable outputs, activation time 0.1 to 300 s

Power supply and connecting wires

The module is powered from the control unit bus and supplies current to the connected control device in the same way. This power output is not protected against overload, so the consumption of the control device must be known in advance. The supply wires may be extended, so the control device does not have to sit right next to the module.

  • Rated consumption 8 mA, maximum 12 mA
  • Output load 50 mA maximum
  • Wires 30 cm, can be extended to a maximum of 3 m

Purpose and limitations

The module does not choose who gives it a command. All that matters is what the control device offers at the terminals: a contact or pulse, and a consumption the power output can handle. How much current the device draws is therefore the first thing you find out about it.

  • Installation may only be carried out by a trained technician holding a valid manufacturer's certificate
  • The module is classified in Security Grade 2, but in a system configured for this grade the control functions are not supported
  • Mounted inside the control device or in a protected installation box