JA-114HN

Bus four-input and four-output module

BUS module with four inputs and four programmable outputs. Each input is configured separately, and the module also provides an auxiliary power supply for connected equipment.

Compatibility

JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K

Check compatibility

Key specifications

Power
from control panel BUS 12 V DC (9 – 15 V)
- Nominal consumption - to calculate backup
11 mA all inputs connected to GND (+ consumption of connected devices)
- Maximal consumption - for cable selection
26 mA (+ consumption of connected devices)
Voltage from +U
12 V DC (9 – 15 V)
Maximum acceptable load from +U (electronic fuse)
< 200 mA
Maximum acceptable current/voltage switched by each output
500 mA/38 V
Max. measured resistance at input
20 kΩ

Basic description

The JA-114HN combines four configurable inputs, four programmable outputs and an auxiliary power supply in a single bus module. It is used to extend wired installations and to renovate older wiring, because it distinguishes the normal, alarm and tamper states of a loop by its resistance. For a single wired detector, the JA-111H TRB is sufficient; the JA-116H is designed for installations with many wired sensors.

  • Four inputs, four programmable outputs and an auxiliary power supply in one module.
  • It connects to the system bus and itself powers the connected equipment, which therefore needs no power supply of its own.
  • The input delay is adjustable from 0.1 s to 300 s.
  • Security grade 2 and environmental class II.

Why choose this product

Inputs, outputs and auxiliary power supply

One module does three jobs: it reads the status of the connected loops, switches its own programmable outputs and powers the equipment that belongs to it. Each input is configured separately according to the detector or contact connected to it. Galvanic isolation of the outputs means that the switched circuit does not share a common ground with the bus, so it can also control third-party equipment.

  • Four inputs: unbalanced, single or double balanced, or roller shutter
  • Four galvanically isolated programmable outputs, max. 500 mA / 38 V
  • Auxiliary power supply 200 mA with electronic fuse

Positions in the system

The module does not report to the control unit as a single peripheral. Each input works separately and takes its own address, so the module occupies a contiguous block of positions. When enrolling, you select the first position of the block and the module takes the rest by itself.

  • Occupies four address positions
  • The three following addresses must be empty
  • Unused inputs can be removed and the position freed

Renovation of older wiring

The module can take over older wiring even with several detectors on one pair of wires. It does not read them as merely closed and open: it measures the resistance and, based on the measured value, recognises the normal state, alarm and tamper. The accuracy of the components used is therefore decisive; a deviation shifts the measurement into the adjacent band.

  • In Oasis mode, normal 700 to 1300 Ω, alarm 1400 to 7800 Ω
  • In Oasis mode, tamper below 600 Ω or above 7900 Ω
  • Loop resistors with a tolerance of no more than 10%

Frequently asked questions

Help us improve the catalog. Missing something, or found a mistake? Let us know.