JA-114HN
Bus four-input and four-output module
BUS module with four inputs and four programmable outputs. Each input is configured separately, and the module also provides an auxiliary power supply for connected equipment.
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Power
- from control panel BUS 12 V DC (9 – 15 V)
- - Nominal consumption - to calculate backup
- 11 mA all inputs connected to GND (+ consumption of connected devices)
- - Maximal consumption - for cable selection
- 26 mA (+ consumption of connected devices)
- Voltage from +U
- 12 V DC (9 – 15 V)
- Maximum acceptable load from +U (electronic fuse)
- < 200 mA
- Maximum acceptable current/voltage switched by each output
- 500 mA/38 V
- Max. measured resistance at input
- 20 kΩ
Basic description
The JA-114HN combines four configurable inputs, four programmable outputs and an auxiliary power supply in a single bus module. It is used to extend wired installations and to renovate older wiring, because it distinguishes the normal, alarm and tamper states of a loop by its resistance. For a single wired detector, the JA-111H TRB is sufficient; the JA-116H is designed for installations with many wired sensors.
- Four inputs, four programmable outputs and an auxiliary power supply in one module.
- It connects to the system bus and itself powers the connected equipment, which therefore needs no power supply of its own.
- The input delay is adjustable from 0.1 s to 300 s.
- Security grade 2 and environmental class II.
Why choose this product
Inputs, outputs and auxiliary power supply
One module does three jobs: it reads the status of the connected loops, switches its own programmable outputs and powers the equipment that belongs to it. Each input is configured separately according to the detector or contact connected to it. Galvanic isolation of the outputs means that the switched circuit does not share a common ground with the bus, so it can also control third-party equipment.
- Four inputs: unbalanced, single or double balanced, or roller shutter
- Four galvanically isolated programmable outputs, max. 500 mA / 38 V
- Auxiliary power supply 200 mA with electronic fuse
Positions in the system
The module does not report to the control unit as a single peripheral. Each input works separately and takes its own address, so the module occupies a contiguous block of positions. When enrolling, you select the first position of the block and the module takes the rest by itself.
- Occupies four address positions
- The three following addresses must be empty
- Unused inputs can be removed and the position freed
Renovation of older wiring
The module can take over older wiring even with several detectors on one pair of wires. It does not read them as merely closed and open: it measures the resistance and, based on the measured value, recognises the normal state, alarm and tamper. The accuracy of the components used is therefore decisive; a deviation shifts the measurement into the adjacent band.
- In Oasis mode, normal 700 to 1300 Ω, alarm 1400 to 7800 Ω
- In Oasis mode, tamper below 600 Ω or above 7900 Ω
- Loop resistors with a tolerance of no more than 10%
Frequently asked questions
Four address positions. Three free positions must remain after the first selected position, otherwise the module overwrites the occupied ones. Unused inputs can be removed and the positions freed.
Unbalanced, single balanced, double balanced and roller shutter, each input separately.
Each programmable output up to 500 mA and 38 V.
Technical specifications
- Power
- from control panel BUS 12 V DC (9 – 15 V)
- - Nominal consumption - to calculate backup
- 11 mA all inputs connected to GND (+ consumption of connected devices)
- - Maximal consumption - for cable selection
- 26 mA (+ consumption of connected devices)
- Voltage from +U
- 12 V DC (9 – 15 V)
- Maximum acceptable load from +U (electronic fuse)
- < 200 mA
- Maximum acceptable current/voltage switched by each output
- 500 mA/38 V
- Max. measured resistance at input
- 20 kΩ
- Max. cable length connected to inputs
- 100 m
- Dimensions
- 77 x 40 x 31 mm
- Weight
- 26 g
- Classification
- security grade 2/environmental class II
- - according to
- EN 50131-1, EN 50131-3 (ACE type B)
- - enviroment
- Indoor general
- - operational temperature range
- -10 to +40 °C
- - average humidity
- 75 %, non-condensing
- - certification body
- Trezor Test s.r.o. (no. 3025)
- Also complies with
- EN 50130-4, EN 55022
Warning
- Always connect the bus with the system power completely switched off. Enrolment overwrites everything that was already on the following positions; therefore check that they are free before enrolling. Pairs of outputs share a common C terminal. The auxiliary power supply has its own limit, which applies separately from the load capacity of the programmable outputs. After the system is switched on, reading the initial states can take up to one minute. In the JA-190PL installation box, the front tamper sensor must be enabled; when mounting in a control unit, disable both tamper sensors of the module. Separate a bus branch outside the protected area with a JA-110T isolator.
Installation example
Always connect the bus with the system power completely switched off.
Place the module in a JA-19xPL series installation box or in a supported control unit.
Connect the bus, the input loops with resistors of the required tolerance, and the load to the outputs.
Enrol the module and check that the following positions are free.
Set the input mode and the function of the programmable outputs and carry out a test.
Related products

JB-110N
Bus PG power output module

JA-111TH
Bus temperature detector

JA-112P
Bus PIR motion detector

JA-110P
Bus PIR motion detector

JA-110P PET
Bus PIR motion detector with basic pet immunity

JA-115P
Bus ceiling PIR motion detector

JA-122PW
Bus dual PIR and MW motion detector

JA-122PB
Bus combined PIR motion and glass break detector

JA-122PC
Bus combined PIR motion detector with 90° photoverification camera

JA-120PC (90)
Bus PIR motion detector with 90° photo-verification camera

JA-120PC
Bus PIR Motion Detector with Camera

JA-111M
Mini bus magnetic detector
Help us improve the catalog
Missing something, or found a mistake? Let us know.