JB-EXT-TH-B
Bus outdoor thermometer
It measures the temperature outdoors or on an external sensor and shows it on keypads and in MyJABLOTRON. It warns when a critical temperature is reached.
Product line
- JABLOTRON 100+
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K, JA-102K
Check compatibilityKey specifications
- Power
- from the bus, 12 V (8 … 36V)
- Low BUS voltage warning
- at 8.5 V
- Current consumption in standby mode
- 1 mA
- Current consumption for cable choice
- 25 mA
- Dimensions
- 90 x 110 x 35 mm
- Weight
- 125 g
- Internal sensor temperature measurement range
- -25 °C to +60 °C
Basic description
You can use the thermometer anywhere the temperature needs to be monitored and logged, or where a warning is needed when a limit value is reached. Linked to a PG output, the thermometer can easily maintain a fixed background temperature of 0 °C. Indoor and outdoor versions are available, in both bus and wireless variants.
- For outdoor and demanding indoor environments
- Option of the JB-TS-PT1000 external sensor for measuring pipes and liquids
- A warning at a set low or high temperature
- Fixed activation temperature (alarm, PG switching) of 0 °C
Why choose this product
An overview of the temperature from anywhere. Even in retrospect
The user sees the current temperature on keypads with a display and in MyJABLOTRON. The temperature is updated every 5 minutes, and MyJABLOTRON shows its progress in a clear graph.
- Temperature history of up to 1 year
- Display of the highest, lowest and average temperature for a selected period
- With the optional JB-TS-PT1000 external sensor, the option of measuring in liquids or pipes
An immediate warning at a critical temperature
In MyJABLOTRON, both a low and a high temperature can be set at which the app sends the user a notification.
- PUSH notification
- SMS
Basic protection against freezing
When the temperature drops, the thermometer can trigger an alarm or switch a PG output for simple background heating, for example at a weekend cottage or in a garage.
- Fixed activation temperature of 0 °C with a hysteresis of 1 °C (switches on at 0 °C, switches off at 1 °C)
- For full temperature regulation, choose from the range of system thermostats
Frequently asked questions
The system reports exceeding or dropping below the set limit as an information message. Outdoors the most common case is frost: the control unit can also respond to the fixed frost-protection activation with an alarm if the engineer sets up such a response.
The measurement itself and the frost-protection activation run in the control unit and do not need the cloud. However, reading the value in the app, setting the limits and messages about exceeding them do go through the cloud, and switching a PG output according to the temperature requires a stable connection between the control unit and the cloud via GSM or LAN. If the connection is lost, the PG output stays in its current state until communication is restored.
Technical specifications
- Power
- from the bus, 12 V (8 … 36V)
- Low BUS voltage warning
- at 8.5 V
- Current consumption in standby mode
- 1 mA
- Current consumption for cable choice
- 25 mA
- Dimensions
- 90 x 110 x 35 mm
- Weight
- 125 g
- Internal sensor temperature measurement range
- -25 °C to +60 °C
- External sensor temperature measurement range
- -50 °C to +200 °C
- Operational temperature
- -40 °C to +70 °C
- Internal sensor temperature measurement range accuracy
- ±0.6 °C
- External sensor temperature measurement range accuracy
- ±1 °C
- IP coverage
- IP53
- Also complies with
- EN 12098-1, EN 60529, EN 50581, EN 60730-1, EN 50130-4, EN 55032 (EN 61000-6-3, EN 55024 (EN 61000-6-1))
Warning
- Always connect the bus with the system power completely switched off. If the bus cable runs outside the protected area, connect the thermometer behind a JA-110T bus isolator located inside the protected area. Protect the thermometer from sunlight, otherwise the measured value may be distorted. Also take care with placement near sources that affect the temperature (heating, fans, air conditioning, fireplace inserts, etc.). If the external probe is disconnected during operation, the thermometer reports a fault; before it returns to measuring with its own sensor, the bus must be restarted.
Installation example
Loosen the screw and separate the top cover from the base.
If you are using an external probe, pull it through the hole in the base together with the bus cable and screw the base to the required place.
Connect the bus cable to the terminal block and the probe, if used, to the terminals for the external sensor; the polarity of the probe does not matter. Always connect the bus with the system power completely switched off.
Close the cover, which connects the pins to the terminal blocks.
Switch on the system power, i.e. both the rechargeable battery and 230 V.
In F-Link, select the required position on the Devices tab, switch on enrolment mode with the Enrol option and confirm the module by double-clicking in the Scan/add new BUS devices option. Then follow the installation manual of the control unit.
Related products

JB-110N
Bus PG power output module

JA-111TH
Bus temperature detector

JA-112P
Bus PIR motion detector

JA-110P
Bus PIR motion detector

JA-110P PET
Bus PIR motion detector with basic pet immunity

JA-115P
Bus ceiling PIR motion detector

JA-122PW
Bus dual PIR and MW motion detector

JA-122PB
Bus combined PIR motion and glass break detector

JA-122PC
Bus combined PIR motion detector with 90° photoverification camera

JA-120PC (90)
Bus PIR motion detector with 90° photo-verification camera

JA-120PC
Bus PIR Motion Detector with Camera

JA-111M
Mini bus magnetic detector
Help us improve the catalog
Missing something, or found a mistake? Let us know.