JB-111TP-AN
Bus room thermostat - anthracite
It controls heating, cooling and ventilation. It allows remote operation and an overview of the temperature and humidity in MyJABLOTRON. It warns when critical values are reached.
Product line
- JABLOTRON 100+
Compatibility
JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Temperature measuring range with external sensor
- -40 to+ 125 C° (± 0.1° C)
- Operating temperature range
- -10 to +50 C°
- Humidity measuring range
- 0 to 100%
- *Temperature controller class
- I. (according to Regulation (EU) No 813/2013)
- *Contribution of controllers to seasonal
- ȠS = 1% (according to Regulation (EU) No 813/2013) *for both parameters in the control panel configuration
- Power supply
- from the control panel bus 12 V DC (10...15 V)
- Rated current consumption
- 5.5 mA
Basic description
The thermostat serves for full regulation of heating and cooling based on measurement of the room temperature as well as the floor temperature. It switches the PG output connected to the heating system until the required temperature is reached. A heating schedule, the option of remote operation and automatic setback linked to alarm events all help to reduce heating costs. The thermostat also measures humidity and, when it rises, it can switch on a fan or increase the output of heat recovery ventilation.
- A single thermostat can control heating, air conditioning and ventilation independently
- Automatic reduction when you leave or when a window is opened
- Current air, floor and humidity values in MyJABLOTRON, including history in clear graphs
- Simple control by buttons, detailed settings and quick remote control from the app
Why choose this product

Automatic operation and remote operation
For use at home or in the office you will make use of program mode, in which the thermostat switches automatically between the comfort and the economical temperature according to a schedule. For technical areas that need a constant temperature, the manual mode, which keeps the set value, is ideal. For holiday properties, the option of switching the thermostat on and off remotely works excellently. Even when switched off, however, it makes sure the temperature does not drop below a safe limit. In the bathroom, the thermostat ventilates automatically after every shower.
- Switching between the operating modes and setting the schedule conveniently from a mobile phone
- Automatic maintenance of a minimum safe temperature in the off mode
- Automatic venting of excess humidity

Lower costs thanks to linking the heating with the alarm
In the Program mode, the thermostat switches automatically to the energy-saving temperature when you leave (when the alarm is switched on). You do not have to think about anything and you still save. According to the set schedule, the temperature returns to the comfort value before you arrive, regardless of the set state.
- Automatic shortening of the comfort period when you leave
- Blocking the heating in a particular room with an open window
- Switching the heating off remotely when your holiday goes on longer

An immediate warning at a critical temperature
An alarm can be set up directly in the system for a selectable critical low or high temperature. The function is excellent wherever the temperature of the space is crucial. For an informative notification without an alarm, the user can set up a warning about a low or high temperature or humidity in MyJABLOTRON.
- PUSH notification, e-mail and SMS
- Reporting to the ARC
- The option of sounding the sirens
Frequently asked questions
It is the anthracite version of the same product: you order it under the full code JB-111TP-AN, and it differs from the basic version neither in its functions nor in its technical parameters.
Yes, once the optional floor sensor is connected. The thermostat then does not let the floor overheat above the set ceiling, but it still controls the normal room temperature according to the air.
Technical specifications
- Temperature measuring range with external sensor
- -40 to+ 125 C° (± 0.1° C)
- Operating temperature range
- -10 to +50 C°
- Humidity measuring range
- 0 to 100%
- *Temperature controller class
- I. (according to Regulation (EU) No 813/2013)
- *Contribution of controllers to seasonal
- ȠS = 1% (according to Regulation (EU) No 813/2013) *for both parameters in the control panel configuration
- Power supply
- from the control panel bus 12 V DC (10...15 V)
- Rated current consumption
- 5.5 mA
- Maximum current draw
- 30 mA
- IP resistance
- IP 31
- Dimensions
- 82 x 82 x 22 mm
- Weight
- 101,1 g
- Operating humidity
- 75 % (non-condensing)
- Environment
- indoor general
- Further complies with
- EN 50130-4, EN 55032, EN IEC 63000
- Recommended screws
- 2x ø 3,5 mm (hemispherical head)
Warning
- Blocking of the output, by an open window for example, does not mean the heating is switched off completely. If the temperature drops to the value set for the off mode, the thermostat overrides the blocking and keeps maintaining that temperature until the blocking ends. The thermostat does not detect tampering, so in alarm systems with Security Grade 2, connect it behind the JA-110T bus isolator. For the full range of functions, the system must be registered in the JABLOTRON Cloud; some functions may be charged for.
Installation example
Always connect the bus with the system power supply completely switched off.
For surface mounting, break the plastic square out of the rear part so that the cables can be pulled through, pull the cables through the square hole and fix the rear part to the wall with two screws.
For partially recessed mounting, pull the cables through the hole in rear part B and fix it into the KU wiring box with two screws, which are not included in the package.
Connect the bus wires, and the floor sensor wires if applicable, to the terminal block; the terminal block for the floor sensor is included in the sensor package.
Fit the top part into the latches and secure it by pulling it down.
Secure the product by turning the locking mechanism clockwise.
Then follow the installation manual of the control unit: in the F-Link program, select the required position on the Devices tab and switch on enrolment mode with the Enrol button.
Open the Scan/add new BUS devices selection and double-click to select the thermostat; it can also be enrolled by entering the full serial number. Then continue to the Internal settings of the peripheral.
Related products

JB-110N
Bus PG power output module

JA-111TH
Bus temperature detector

JA-112P
Bus PIR motion detector

JA-110P
Bus PIR motion detector

JA-110P PET
Bus PIR motion detector with basic pet immunity

JA-115P
Bus ceiling PIR motion detector

JA-122PW
Bus dual PIR and MW motion detector

JA-122PB
Bus combined PIR motion and glass break detector

JA-122PC
Bus combined PIR motion detector with 90° photoverification camera

JA-120PC (90)
Bus PIR motion detector with 90° photo-verification camera

JA-120PC
Bus PIR Motion Detector with Camera

JA-111M
Mini bus magnetic detector
Help us improve the catalog
Missing something, or found a mistake? Let us know.