JB-128N
Module for controlling floor heating heads
A bus module that switches the zoning heads of hot-water heating, the circulation pump and the heat source. Each of its heating outputs copies the state of the assigned PG output of the control unit. It is installed at the underfloor heating manifold, where the heads of the individual heating loops are located.
Compatibility
JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Supply voltage
- 230 V AC, 50 Hz
- Power consumption of the device (without heads and pump)
- max. 2.3 W / idle 0.8 W
- Maximum supply current
- 1.8 A
- Recommended protection (circuit breaker)
- 4A type B
- Connection to the system
- 12 V DC (8 to 15 V) control panel bus
- Supply voltage
- 230 V AC, 50 Hz
- Maximum power input
- 2 W
Basic description
Two different devices can move a valve of a hot-water system from a PG output of the control unit. The JB-128N is a wired module installed at the underfloor heating manifold that controls the heads of all its heating loops. The JB-150N-HEAD is a wireless valve head fitted directly onto a single valve of the hot-water system. The choice is therefore about scope: all the loops of the manifold, or a single valve.
- Heating and security run on a single system: the control unit decides when each loop heats, and the module carries out its decision.
- It connects to the control unit bus and additionally needs its own permanent 230 V mains supply.
- One module serves twelve heating circuits and, in addition, separately switches the circulation pump and the heat source.
- The module handles protective functions by itself: outside the heating season it regularly opens the heads so that they do not seize up, and if the connection with the control unit is lost, it first switches the heating outputs off to prevent overheating and later switches them on again to prevent freezing.
Why choose this product
Control of heating circuits
The module does not decide on the temperature. Each of its heating outputs has an assigned PG output of the control unit and copies its state; when the PG switches on is decided by the system thermostats and sensors in the individual rooms. The module controls the auxiliary outputs for the pump and the heat source itself, according to whether at least one heating output is active, with a delay and an overlap that are set in the peripheral's internal settings. In addition, a slide switch accessible through the top cover enables the Open all manual mode, in which the module heats permanently even without an available control unit, for example when drying out a new building.
- Each output copies one selected PG; one PG can control several outputs, but not the other way round
- Assign the PG output controlled by the thermostat in a given room to the output that switches the head of that room's heating loop
- The circulation pump is switched by a voltage output, the heat source by a volt-free contact; both can handle a current of up to 1 A
What connects to the module
The module sits between the control unit and the heating system: on one side the bus and the mains supply, on the other the heads of the individual loops and the auxiliary outputs for the pump and the heat source. The power supply to the heating outputs runs through the safety thermostat terminals, so activating the safety thermostat disconnects them. The pump and the heat source can also be switched by relay modules of the JA-100+ range, if required.
- Each heating output takes a mains-voltage thermoelectric head with a continuous power input of no more than 2 W
- The module draws no more than 10 mA continuously from the control panel bus; common protection of the heating outputs is provided by a 0.8 A type F fuse
- The external safety thermostat is optional; if you do not use it, its terminals must be permanently bridged with an insulated conductor with a cross-section of at least 1.5 mm²
Environment, protective functions and bus
The module belongs in an indoor – general environment, and its mounting base can be fixed in several ways, so it fits next to the underfloor heating manifold or into a distribution board.
- Without mains power the module does not work at all, and the control unit reports it as lost
- Three protective functions run by themselves: anti-seizing every Sunday at 02:00 for five minutes, and overheating protection by switching the outputs off after 20 minutes without communication. For frost protection, the module switches the outputs on again after 24 hours without communication and repeats this every 4 hours; these are default times and can be changed
- The module has no tamper protection, so its wired installation must be run through a bus isolator or connected to a separate bus interface directly on the control unit
Frequently asked questions
You need a source of demand. The room temperature must be monitored by a system thermostat or sensor that controls one of the PG outputs in the control unit; the module then opens the head of the relevant loop according to that output. The module controls the circulation pump and the heat source by itself.
The heating does not stop permanently. For safety, the module first switches the heating outputs off, and if the outage continues, it starts switching them on periodically by itself so that the system does not freeze. As soon as the connection is restored, it returns to control by the control unit.
Technical specifications
- Supply voltage
- 230 V AC, 50 Hz
- Power consumption of the device (without heads and pump)
- max. 2.3 W / idle 0.8 W
- Maximum supply current
- 1.8 A
- Recommended protection (circuit breaker)
- 4A type B
- Connection to the system
- 12 V DC (8 to 15 V) control panel bus
- Supply voltage
- 230 V AC, 50 Hz
- Maximum power input
- 2 W
- Maximum current consumption
- 300 mA after 200 ms
- Output protection for headers
- 0.8 A, type T
- Number of outputs
- 12
- NC contact load capacity
- 1 A / 250 V AC
- Maximum switching current
- 1 A / 230 V AC
- Protection class
- II
- Mounting type
- Wall / pipe / DIN rail
- Dimensions
- 245 x 90 x 50 mm
- Degree of protection IP
- IP20
- Environment
- indoor general
- Relative humidity
- max. 85 % (non-condensing)
- Operating temperatures (ambient)
- 5° C to +45 °C
- In compliance with
- EN 50130-4, EN 55032, EN 62368-1, EN IEC 63000, EN 60730-1
Warning
- Always connect the bus with the system power completely switched off, and disconnect the module's power supply before opening the cover. If the safety thermostat terminals are not bridged and no thermostat is connected, the heating outputs remain without power and the module will not switch. The Open all manual mode does not bypass an open safety thermostat, so it cannot be used as a substitute for repairing it. If the module reports an error, check both the output fuse and the protective thermostat; the module does not distinguish between them.
Installation example
Wiring is a job for a trained technician with a valid JABLOTRON certificate and is carried out with the system power completely switched off.
Choose the installation location, unscrew the top lid and remove the middle part from the mounting base.
Fix the base with PE ties to the pipes of the underfloor heating manifold, to a DIN rail or to the wall.
Connect the bus wires, the break contact of the safety thermostat, the power supply cable and, if applicable, the pump and boiler wires; route the cables and secure them with the fixing clip at the relevant terminal block.
Fit the middle part with its bottom edge behind the lugs of the base and fold it down until the latches click into place.
Connect the wires of the thermoelectric heads to the terminal blocks provided and thread the cable through the labyrinth.
Fit the transparent lid and connect the power supply by switching on the circuit breaker.
In the F-Link program, select the required position on the Devices tab and switch on enrolment mode with the Enrol button.
Select Scan/add new BUS devices and double-click the module; with a large number of peripherals, press the Learn button directly on the module with a screwdriver. It can also be enrolled by entering the full serial number.
In the peripheral's internal settings, assign each output its PG output and set the delay and overlap of the pump and the heat source.
Related products

JB-150N-HEAD
Wireless thermostatic head

JB-EXT-TH-R
Wireless outdoor thermometer

JA-111TH
Bus temperature detector

JA-151TH
Wireless temperature detector

JB-EXT-TH-B
Bus outdoor thermometer

JB-111TP
Bus room thermostat

JB-111TP-AN
Bus room thermostat - anthracite

JB-151TP
Wireless room thermostat

JB-151TP-AN
Wireless room thermostat - anthracite

JB-111TH
Bus temperature and humidity sensor with thermostat function

JB-111TH-AN
Bus temperature and humidity sensor with thermostat function - anthracite

JB-112TH
BUS temperature, humidity and CO₂ sensor with thermostat function
Help us improve the catalog
Missing something, or found a mistake? Let us know.