JB-128N

Module for controlling floor heating heads

A bus module that switches the zoning heads of hot-water heating, the circulation pump and the heat source. Each of its heating outputs copies the state of the assigned PG output of the control unit. It is installed at the underfloor heating manifold, where the heads of the individual heating loops are located.

Compatibility

JA-103K, JA-107K, JA-108K

Check compatibility

Key specifications

Supply voltage
230 V AC, 50 Hz
Power consumption of the device (without heads and pump)
max. 2.3 W / idle 0.8 W
Maximum supply current
1.8 A
Recommended protection (circuit breaker)
4A type B
Connection to the system
12 V DC (8 to 15 V) control panel bus
Supply voltage
230 V AC, 50 Hz
Maximum power input
2 W

Basic description

Two different devices can move a valve of a hot-water system from a PG output of the control unit. The JB-128N is a wired module installed at the underfloor heating manifold that controls the heads of all its heating loops. The JB-150N-HEAD is a wireless valve head fitted directly onto a single valve of the hot-water system. The choice is therefore about scope: all the loops of the manifold, or a single valve.

  • Heating and security run on a single system: the control unit decides when each loop heats, and the module carries out its decision.
  • It connects to the control unit bus and additionally needs its own permanent 230 V mains supply.
  • One module serves twelve heating circuits and, in addition, separately switches the circulation pump and the heat source.
  • The module handles protective functions by itself: outside the heating season it regularly opens the heads so that they do not seize up, and if the connection with the control unit is lost, it first switches the heating outputs off to prevent overheating and later switches them on again to prevent freezing.

Why choose this product

Control of heating circuits

The module does not decide on the temperature. Each of its heating outputs has an assigned PG output of the control unit and copies its state; when the PG switches on is decided by the system thermostats and sensors in the individual rooms. The module controls the auxiliary outputs for the pump and the heat source itself, according to whether at least one heating output is active, with a delay and an overlap that are set in the peripheral's internal settings. In addition, a slide switch accessible through the top cover enables the Open all manual mode, in which the module heats permanently even without an available control unit, for example when drying out a new building.

  • Each output copies one selected PG; one PG can control several outputs, but not the other way round
  • Assign the PG output controlled by the thermostat in a given room to the output that switches the head of that room's heating loop
  • The circulation pump is switched by a voltage output, the heat source by a volt-free contact; both can handle a current of up to 1 A

What connects to the module

The module sits between the control unit and the heating system: on one side the bus and the mains supply, on the other the heads of the individual loops and the auxiliary outputs for the pump and the heat source. The power supply to the heating outputs runs through the safety thermostat terminals, so activating the safety thermostat disconnects them. The pump and the heat source can also be switched by relay modules of the JA-100+ range, if required.

  • Each heating output takes a mains-voltage thermoelectric head with a continuous power input of no more than 2 W
  • The module draws no more than 10 mA continuously from the control panel bus; common protection of the heating outputs is provided by a 0.8 A type F fuse
  • The external safety thermostat is optional; if you do not use it, its terminals must be permanently bridged with an insulated conductor with a cross-section of at least 1.5 mm²

Environment, protective functions and bus

The module belongs in an indoor – general environment, and its mounting base can be fixed in several ways, so it fits next to the underfloor heating manifold or into a distribution board.

  • Without mains power the module does not work at all, and the control unit reports it as lost
  • Three protective functions run by themselves: anti-seizing every Sunday at 02:00 for five minutes, and overheating protection by switching the outputs off after 20 minutes without communication. For frost protection, the module switches the outputs on again after 24 hours without communication and repeats this every 4 hours; these are default times and can be changed
  • The module has no tamper protection, so its wired installation must be run through a bus isolator or connected to a separate bus interface directly on the control unit