CC-01
Bus cable
Installation bus cable with a reinforced power pair for backbone wiring of the JABLOTRON system. It can also carry the power supply for more distant peripherals over longer runs.
Key specifications
- 1 × 2 × 24 AWG (0,2 mm2)
- max. resistance of dc conductor at 20 °C 97 Ω/km
- 1 × 2 × 20 AWG (0,5 mm2)
- max. resistance of dc conductor at 20 °C 38 Ω/km
Basic description
Four cables answer the same question, each in a different way: how much current is left at the end of the run and how far the bus can reach. The higher the current, the shorter the run can be; a thicker power pair carries current further. One of the cables also has two auxiliary pairs, another has a sheath with increased fire resistance.
- The power supply reaches even the far end of the bus, provided the run length matches the consumption of the connected peripherals.
- The conductor colours match the terminal colours, which reduces the risk of mix-ups during wiring.
- Handles 400 m at a total consumption of 50 mA, or only 50 m at 500 mA.
Why choose this product
Conductors and their purpose
One pair of conductors transmits data between the control unit and the peripherals; the other is thicker and carries the power supply. It is the thicker pair that determines how far from the control unit a peripheral can be placed.
- 4 conductors, 0.5 mm² power pair, 0.2 mm² data pair, outer diameter 4.5 mm
- Pack of 300 m
- Length markings every 1 m along the entire cable
Role in the system
It runs the bus from the control unit to the peripherals and can also carry components with high consumption, such as a siren.
- Backbone wiring or sections with higher consumption
- Recommended for newly laid wiring
- Run it inside the protected premises; any section outside them must be separated by a bus isolator
Conductor resistance and voltage drop
Conductor resistance increases with run length and determines the voltage drop at the far end of the bus.
- Power pair resistance approximately 7.54 Ω per 100 m
- The stated resistance applies to the entire cable loop, out and back
- The voltage at a peripheral must not drop below 10 V; the maximum permissible drop along the cable is 2.0 V
Frequently asked questions
The CC-01 has a reinforced power pair for backbone wiring and higher consumption; the CC-02 has two thinner pairs for branches and shorter sections.
Yes, its thicker power pair handles this better than the CC-02.
Technical specifications
- 1 × 2 × 24 AWG (0,2 mm2)
- max. resistance of dc conductor at 20 °C 97 Ω/km
- 1 × 2 × 20 AWG (0,5 mm2)
- max. resistance of dc conductor at 20 °C 38 Ω/km
Warning
- Always connect the bus with the system's power supply completely switched off. At higher current over a longer run, the voltage drop increases; check the maximum length for the given current in the parameter table. Never join the ends of individual branches; no closed loop may be formed on any conductor, not even on the common GND conductor.
Installation example
Always connect the bus with the control unit's power supply completely switched off and the back-up battery disconnected.
Connect the conductors according to the colours of the bus terminals (red, yellow, green, black).