CC-03

Bus cable

Installation bus cable with its own bus pair and two auxiliary pairs for connecting peripherals outside the bus. The auxiliary pairs are suitable, for example, for magnet contacts or tamper loops.

Key specifications

Specification
1 × 2 × 20 AWG (0,5 mm 2 ) 3 × 2 × 24 AWG (0,2 mm 2 )

Basic description

Four cables answer the same question, each in a different way: how much current is left at the end of the run and how far the bus can reach. The higher the current, the shorter the run can be; a thicker power pair carries current further. One of the cables also has two auxiliary pairs, another has a sheath with increased fire resistance.

  • The power supply reaches even the far end of the bus, provided the run length matches the consumption of the connected peripherals.
  • The conductor colours match the terminal colours, which reduces the risk of mix-ups; two additional pairs carry signals outside the bus.
  • Handles 400 m at a total consumption of 70 mA, or only 50 m at 800 mA.

Why choose this product

Conductors and their purpose

One pair of conductors transmits data; the other is thicker and carries the power supply. The remaining two pairs stay free for signals outside the bus, for example from magnet contacts or tamper loops.

  • 8 conductors, 0.7 mm² power pair, data pair and two auxiliary pairs of 0.3 mm² each, outer diameter 6.4 mm
  • EasyReel reel 250 m
  • Length markings every 1 m along the entire cable

Role in the system

A single cable thus carries both the bus and the auxiliary signals, without a second cable along the same route.

  • Backbone wiring with two auxiliary pairs for peripherals
  • Recommended for newly laid wiring
  • Run it inside the protected premises; any section outside them must be separated by a bus isolator

Conductor resistance and voltage drop

Conductor resistance increases with run length and determines the voltage drop at the far end of the bus.

  • Power pair resistance approximately 7.05 Ω per 100 m
  • The stated resistance applies to the entire cable loop, out and back
  • The voltage at a peripheral must not drop below 10 V; the maximum permissible drop along the cable is 2.0 V