CC-03
Bus cable
Installation bus cable with its own bus pair and two auxiliary pairs for connecting peripherals outside the bus. The auxiliary pairs are suitable, for example, for magnet contacts or tamper loops.
Key specifications
- Specification
- 1 × 2 × 20 AWG (0,5 mm 2 ) 3 × 2 × 24 AWG (0,2 mm 2 )
Basic description
Four cables answer the same question, each in a different way: how much current is left at the end of the run and how far the bus can reach. The higher the current, the shorter the run can be; a thicker power pair carries current further. One of the cables also has two auxiliary pairs, another has a sheath with increased fire resistance.
- The power supply reaches even the far end of the bus, provided the run length matches the consumption of the connected peripherals.
- The conductor colours match the terminal colours, which reduces the risk of mix-ups; two additional pairs carry signals outside the bus.
- Handles 400 m at a total consumption of 70 mA, or only 50 m at 800 mA.
Why choose this product
Conductors and their purpose
One pair of conductors transmits data; the other is thicker and carries the power supply. The remaining two pairs stay free for signals outside the bus, for example from magnet contacts or tamper loops.
- 8 conductors, 0.7 mm² power pair, data pair and two auxiliary pairs of 0.3 mm² each, outer diameter 6.4 mm
- EasyReel reel 250 m
- Length markings every 1 m along the entire cable
Role in the system
A single cable thus carries both the bus and the auxiliary signals, without a second cable along the same route.
- Backbone wiring with two auxiliary pairs for peripherals
- Recommended for newly laid wiring
- Run it inside the protected premises; any section outside them must be separated by a bus isolator
Conductor resistance and voltage drop
Conductor resistance increases with run length and determines the voltage drop at the far end of the bus.
- Power pair resistance approximately 7.05 Ω per 100 m
- The stated resistance applies to the entire cable loop, out and back
- The voltage at a peripheral must not drop below 10 V; the maximum permissible drop along the cable is 2.0 V
Frequently asked questions
They are used for auxiliary conductors outside the bus, for example for magnet contacts or tamper loops; the specific use is determined by the installation design.
It is designed for the newer generation of the JABLOTRON system. For older bus control units, use the CC-01, CC-02 or the fire-resistant CC-11.
Technical specifications
- Specification
- 1 × 2 × 20 AWG (0,5 mm 2 ) 3 × 2 × 24 AWG (0,2 mm 2 )
Warning
- Always connect the bus with the system's power supply completely switched off. Determine the load on the auxiliary pairs according to the instructions of the connected device, not by estimate. Do not confuse it with the fire-resistant CC-11 cable, which has no auxiliary pairs. Never join the ends of individual branches; no closed loop may be formed on any conductor, not even on the common GND conductor.
Installation example
Always connect the bus with the control unit's power supply completely switched off and the back-up battery disconnected.
Connect the conductors according to the colours of the bus terminals (red, yellow, green, black).
Distinguish the bus pair and the two auxiliary pairs by their colour coding; check the load on the auxiliary pairs according to the instructions of the connected device.