CC-02
Bus cable
Installation bus cable with two identical pairs for branches from the backbone wiring and shorter bus sections of the JABLOTRON system. Neither of the two pairs is reinforced.
Key specifications
- 2 × 2 × 24 AWG (0,2 mm2)
- max. resistance of dc conductor at 20 °C 97 Ω/km
Basic description
Four cables answer the same question, each in a different way: how much current is left at the end of the run and how far the bus can reach. The higher the current, the shorter the run can be; a thicker power pair carries current further. One of the cables also has two auxiliary pairs, another has a sheath with increased fire resistance.
- The power supply reaches even the far end of the bus, provided the run length matches the consumption of the connected peripherals.
- The conductor colours match the terminal colours, which reduces the risk of mix-ups during wiring.
- Handles 200 m at a total consumption of 25 mA, or only 30 m at 300 mA.
Why choose this product
Conductors and their purpose
Both pairs of conductors are the same thickness; the power pair is not reinforced. Over a longer run, the voltage therefore drops faster and the cable is better suited to shorter sections.
- 4 conductors, both pairs 0.2 mm², outer diameter 4.1 mm
- Pack of 300 m
- Length markings every 1 m along the entire cable
Role in the system
It connects components with low consumption, typically detectors, at the ends of the bus.
- Branches from the backbone wiring or shorter sections
- Recommended for newly laid wiring
- Run it inside the protected premises; any section outside them must be separated by a bus isolator
Conductor resistance and voltage drop
Conductor resistance increases with run length and determines the voltage drop at the far end of the bus.
- Power pair resistance approximately 19.32 Ω per 100 m
- The stated resistance applies to the entire cable loop, out and back
- The voltage at a peripheral must not drop below 10 V; the maximum permissible drop along the cable is 2.0 V
Frequently asked questions
The CC-02 has two identical thinner pairs for branches and shorter sections; the CC-01 additionally has a reinforced power pair for backbone wiring.
It is not recommended for a longer run with higher consumption, because it does not have a reinforced power pair. For backbone wiring, choose the CC-01.
Technical specifications
- 2 × 2 × 24 AWG (0,2 mm2)
- max. resistance of dc conductor at 20 °C 97 Ω/km
Warning
- Always connect the bus with the system's power supply completely switched off. At higher current over a longer run, the voltage drop increases; check the maximum length for the given current in the parameter table. For backbone wiring or higher consumption, choose the CC-01. Never join the ends of individual branches; no closed loop may be formed on any conductor, not even on the common GND conductor.
Installation example
Always connect the bus with the control unit's power supply completely switched off and the back-up battery disconnected.
Connect the conductors according to the colours of the bus terminals (red, yellow, green, black).