JA-110T
Bus short-circuit isolator module
Bus isolator that separates a branch running outside the protected area from the rest of the system. In the event of overload or a voltage drop, it disconnects this branch and the inner part of the bus keeps working.
Compatibility
JA-100K, JA-101K, JA-106K, JA-103K, JA-107K, JA-108K
Check compatibilityKey specifications
- Power
- from control panel digital bus 12 V (9 … 15 V)
- Current consumption in standby mode
- 5 mA
- Current consumption for cable selection
- 5 mA
- Maximum allowed current in the outer bus branch
- max 250 mA
- Classification
- Grade II according to EN 50131-1, EN 50131-3,
- Operational environment according to EN 50131-1
- II.Indoor general
- Operating temperature range
- -10 °C to 40 °C
Basic description
The JA-110T is a non-addressable isolator that divides the bus. It separates the outer branch from the inner protected part, so if the outdoor line is short-circuited or overloaded, the inner system keeps working. It is not enrolled to the system and occupies no position, so any number of them can be used in an installation, but never in series one after another. The opposite is the addressable JA-110Z splitter, which joins the bus instead and itself occupies one position.
- A fault on the outer line does not stop the system inside. The isolator separates the outer bus branch from the inner one.
- It is powered directly from the bus and needs no power supply of its own.
- Disconnects a faulty branch by itself. Above 250 mA or below 9 V, it disconnects the output branch for 5 seconds.
- Recommended wherever the bus leaves the protected area. In the same way, you can separate individual floors or wings of a building from each other.
Why choose this product
Isolation of a bus branch
A line that leaves the protected area is the most vulnerable part of the whole bus: it is furthest from the control unit and closest to whatever can harm it. Without separation, such a fault shows up throughout the system, because the bus is shared by all devices. The isolator puts a stop to it at the boundary between outside and inside.
- Disconnects the output branch for 5 seconds at a consumption above 250 mA
- Reacts in the same way to an input voltage drop below 9 V
- Permanent disconnection is indicated by the yellow LED lighting continuously
Power supply and connection
The terminals marked INSIDE belong to the control unit side, the OUTSIDE terminals to the branch running outside the protected area. This wiring determines which side the isolator disconnects in the event of a fault and which side remains in operation. It can be placed in a JA-19xPL series installation box, in the control unit enclosure or in a standard electrical installation box.
- Nominal voltage 12 V, range 9 to 15 V
- Standby consumption 5 mA; 360 mA applies for cable selection
- Dimensions 38 × 42 × 14 mm, weight 15 g
Use in the installation
Whether the isolator contributes to the classification of the whole assembly is decided not by the module itself but by what it is enclosed in and what complements it. Likewise, the environment in which it may operate must be documented. And the longer the cable to the module, the more it pays to calculate what actually reaches its terminals.
- Security Grade 2 applies only in a JA-194PL or JA-195PL box together with the JA-111H TRB
- Environmental class II, operating temperature -10 to +40 °C
- On a long line, make sure the input voltage is sufficient
Frequently asked questions
It separates the outer bus branch from the inner part of the system. If the outdoor line is short-circuited or overloaded, the isolator disconnects this branch and the rest of the system keeps working.
No, it is not enrolled to the system and occupies no address. You can therefore use any number of them in an installation.
Security Grade 2 applies only when mounted in a JA-194PL or JA-195PL box together with the JA-111H TRB module. The classification is therefore tied to a specific assembly, not to the module itself.
Technical specifications
- Power
- from control panel digital bus 12 V (9 … 15 V)
- Current consumption in standby mode
- 5 mA
- Current consumption for cable selection
- 5 mA
- Maximum allowed current in the outer bus branch
- max 250 mA
- Classification
- Grade II according to EN 50131-1, EN 50131-3,
- Operational environment according to EN 50131-1
- II.Indoor general
- Operating temperature range
- -10 °C to 40 °C
- Also complies with
- EN 50130-4, EN 55022
Warning
- Always connect the bus with the system power completely switched off. The module itself should always remain inside the protected area, even though it separates a branch running outside. Do not confuse the standby consumption of the module, the value for cable dimensioning and the maximum current of the outer branch; these are three different figures.
Installation example
Always connect the bus with the system power completely switched off.
Place the module inside the protected area, in a JA-19xPL series installation box, in the control unit enclosure or in a standard electrical installation box.
Connect the INSIDE terminals to the control unit side and the OUTSIDE terminals to the branch running outside the protected area.
Do not connect isolators in series one after another.