RB-524-DIN
Universal power relay for DIN rail
Universal power relay for DIN rail mounting in a distribution board. Applying a control voltage to the input terminals switches over the output contact, which is galvanically isolated from the control circuit. It is not a peripheral of any particular control unit and is controlled directly by the voltage signal you apply to the terminals.
Key specifications
- Operational voltage range
- from 5 to 24 V DC
- Standby current
- 5 V - 80 mA, 12 V - 40 mA, 24 V - 25 mA
- (galvanically separated from control terminals)
- protection class II
- - maximum switching voltage
- 250 V AC/24 V DC
- - resistive load (cos φ=1)
- max. 16 A
- - inductive, capacitive load (cos φ=0,4)
- max. 8 A
- - halogen lights
- max. 1000 W
Basic description
Compared with the AC-160-C and AC-160-DIN wireless multifunction relays, the difference is fundamental: the RB-524-DIN is not enrolled into any control unit and does not occupy a position in it. It is controlled directly by a voltage signal applied to the input terminals. Where wireless control from the system is needed, the AC-160-DIN belongs there instead.
- A control voltage applied to the input terminals switches over the output contact, which is galvanically isolated from the control circuit.
- It is not a peripheral of any particular control unit; it works with any compatible source of DC control voltage.
- Switches voltages up to 250 V AC or up to 24 V DC, resistive loads up to 16 A, inductive and capacitive loads up to 8 A, halogen lighting up to 1000 W and DC power up to 384 W. This is functional single-pole switching that does not provide safe disconnection.
Why choose this product
What happens when the control voltage is applied
As soon as you apply the control voltage to the input terminals, the relay switches over the output contact and the red LED lights up.
- The control input works in the range 5 to 24 V DC, with a current draw of 80 mA at 5 V, 40 mA at 12 V and 25 mA at 24 V.
- The output contact is a changeover contact (NO-C-NC), galvanically isolated from the control circuit and rated for a test voltage of 4 kV.
- The minimum switched DC power is 0.5 W.
Where the relay is connected
The relay is mounted on a DIN rail in a distribution board and is connected on both sides: at the input to the control voltage, at the output to the switched circuit.
- The switched circuit may be protected by a fuse of at most 16 A.
Where it is mounted and what design it has
The relay is intended for an indoor environment. It takes up space on the rail according to its dimensions, and conductors of common cross-sections are connected to its terminals.
- A maximum of 2× 1.5 mm² or 1× 2.5 mm² conductors can be connected to each terminal; the relay's dimensions are 18 × 90 × 65 mm and its weight is 50 g.
- IP20 protection rating, protection class II, DIN rail profile according to EN 60715; heat dissipation into the distribution board 2.0 W.
- The operating temperature range is −10 °C to +40 °C.
Frequently asked questions
No. It is a universal relay controlled by any compatible DC signal in the range 5 to 24 V. It is used with the JABLOTRON system and also outside it.
Technical specifications
- Operational voltage range
- from 5 to 24 V DC
- Standby current
- 5 V - 80 mA, 12 V - 40 mA, 24 V - 25 mA
- (galvanically separated from control terminals)
- protection class II
- - maximum switching voltage
- 250 V AC/24 V DC
- - resistive load (cos φ=1)
- max. 16 A
- - inductive, capacitive load (cos φ=0,4)
- max. 8 A
- - halogen lights
- max. 1000 W
- - DC
- 384 W
- - minimum acceptable relay output through-wattage (DC)
- 0.5 W
- Cross section of connecting wires
- max. 2 x 1,5 mm 2 max. 1 x 2,5 mm 2
- Dimensions, weight
- 18 x 90 x 65 mm, 50 g
- Operational environment
- indoor general
- Operational temperature environment
- -10 °C to + 40 °C
- IP covering
- IP-20
- Also complies with
- EN 50130-4, EN 55022, EN 60950-1 DIN rail EN60715
Warning
- With an inductive or capacitive load, the relay can withstand considerably less than with a resistive load. Therefore check the type of appliance being connected, not just the current. In addition, the relay does not provide safe disconnection; where the design requires it, it must be provided by another element of the installation.
Installation example
Mains-powered devices may only be connected by a qualified person.
Fit the relay onto the DIN rail in the distribution board.
Always connect the control conductors and the conductors of the switched circuit with the power supply completely switched off.
Route the switched circuit through protection of at most 16 A.
Related products

JA-150N
Wireless power output module PG

JA-151N
Wireless signal output module PG

JB-110N
Bus PG power output module

AC-160-C
Mounting-box-fitted wireless multifunctional power relay

JB-160N-PLUG
Smart Wireless Plug (French)

JB-164N-PLUG
Smart Socket with Consumption Measurement (French)

JA-110N-DIN
Bus DIN power output module

JB-111N
Bus signal PG output module

JB-118N
Bus signal PG output module - 8 outputs

JA-120N
Bus module for control of an electric lock

JB-162N-PLUG
Wireless plug with external output (French)

AC-160-DIN
Wireless multifunctional relay for DIN-rail installation
Help us improve the catalog
Missing something, or found a mistake? Let us know.